Detailed Castle Series Description
Features:
a) True online double conversion technology
b) Wide input voltage range
c) Zero transfer time
d) Protection against all types of power problems
e) No add - on CNTL unit required for parallel connection
f) Models: C6K, C6KS, C10K, C10KS
g) Rated power: 6kVA / 4.2kW, 10kVA / 7kW, 6kVA / 4.2kW, 10kVA / 7kW
h) Input: nominal voltage 220V AC
i) Voltage range: 176~276V AC
j) Frequency range: 46~54Hz
k) Power factor: 0.98
l) Output voltage: 220V AC
m) Frequency:
1) Synchronized 46~54Hz (line )
2) 50Hz (battery )
n) Wave form: sinusoidal
o) Voltage distortion: 2% under linear load
p) Overload capability: 105%~130% for 10 min
q) Current crest ratio: 3:1
r) Battery & charger: type valve regulated, sealed, lead - acid
s) External battery bank nominal voltage: 240V DC
t) Backup time (full ) 7min, 5min depends on the external battery capacity
u) Transfer time: 0ms
v) LED indicators: status load level / battery level, utility power, battery, inverter, overload,
bypass, fault
w) Audible alarms: on battery mode, overload, battery low, fault
x) Communications interface: RS - 232 serial interface (DB - i)
y) Intelligent slot
z) Parallel port: availability of up to three units in parallel for power redundancy and
load sharing
) Operating temperature: 0~40oC
) Operating humidity: 20~90% non - condensing
) Applications: servers, data - centre, sensitive electronic
equipment, critical network devices, telecom
) N. W.: 84, 35, 93, 38kg
) Dimensions (W x D x ): 260 x 570 x 717mm
) Specifications are subject to change without notice
Features (Castle Series N+):
a) Models: 3C10KS, 3C15KS, 3C20KS
b) Rated power: 10kVA / 7kW, 15kVA / 10.5kW, 20kVA / 14kW
c) Input nominal voltage: 380V AC
d) Voltage range: 304~478V AC
e) Frequency range: 46~54Hz
f) Power factor: 0.95
g) Output voltage: 220V AC
h) Frequency:
1) Synchronized 46~54Hz (line )
2) 50Hz (battery )
i) Wave form: sinusoidal
j) Voltage distortion: 2% under linear load
k) Overload capability: 105%~130% for 10 min.
l) Current crest ratio: 3:1
m) Battery & charger: nominal voltage 240V DC
n) Backup time depends on the external battery capacity
o) Transfer time: 0ms
p) LED indicators: status load level / battery level, utility power, battery, inverter, overload,
bypass, fault
q) Audible alarms: on battery mode, overload, battery low, fault
r) Communications interface: RS - 232 serial interface (DB - i)
s) Intelligent slot
t) Parallel port: availability of up to three units in parallel for power redundancy and
load sharing
u) Operating temperature: 0~40oC
v) Operating humidity: 20~90% non - condensing
w) Applications: servers, data - centre, sensitive electronic
equipment, critical network devices, telecom
x) N. W.: 39, 55kg
y) Dimensions (W x D x ): 260 x 570 x 717mm
If you would like more information about Castle Series, please contact us or visit our website for more details.
|